  • A comparative study on ground source heat pump systems in Mersin

A comparative study on ground source heat pump systems in Mersin

Authors : Bengi GOZMEN, Elif TURNA DİLSEL, Onur GÜVEN
Pages : 146-151
Doi:10.26701/ems.1271520
View : 81 | Download : 43
Publication Date : 2023-09-20
Article Type : Research Paper
Abstract :In present study, the thermal performance of a ground source heat pump system was investigated . A ground source heat pump system was designed theoretically in order to heat a detached house with the area of 168.7 m2 in Mersin province of Turkey. The heat loss of the house was assessed to be 10 kW. The coefficient of performance insert ignore into journalissuearticles values(COP); of ground source heat pump system using R134a was compared with that of the heat pump system using R410a. The COP of ground source heat pump system using the working fluid R134a was calculated as 7.24 while the COP of heat pump system using the R410a was determined as 6.66. The required length of heat exchanger for the ground source heat pump systems working with R410a was longer than that of the ground source heat pump system working with R134a .
Keywords : Heat pump system, heat loss, efficiency, working fluid

ORIGINAL ARTICLE URL

* There may have been changes in the journal, article,conference, book, preprint etc. informations. Therefore, it would be appropriate to follow the information on the official page of the source. The information here is shared for informational purposes. IAD is not responsible for incorrect or missing information.